A
C
C
B
B
A
The product must not be used in this region.
Flanged EN 1092 PN40 and ASME 300.
Flanged ASME 150 and JIS / KS 20K.
Pressure bar g
A - B
A - C
Pressure bar g
Body design conditions
PMA Maximum allowable pressure
TMA Maximum allowable temperature
Minimum allowable temperature
PMO Maximum operating pressure
TMO Maximum operating temperature
Minimum operating temperature
Note: For lower operating temperatures consult Spirax Sarco
DPMX Maximum differential pressure
The maximum differential pressure depends on the specific
gravity of the liquid being drained.
Designed for a maximum cold hydraulic test pressure of:
CA46
CA46S
CA46
CA46S
Specific gravity
PN40
40 bar g @ 80°C
200°C @ 29 bar g
400°C @ 20 bar g
0°C
40 bar g @ 80°C
Trap
CA46-32
CA46S-4.5
CA46S-10
CA46S-14
CA46S-21
CA46S-32
1.0
0.9
32.0
32.0
4.5
4.5
10.0
9.5
14.0
14.0
21.0
19.0
32.0
30.0
PN40
ASME 300
ASME 150
JIS/KS20K
0.8
29.0
4.5
6.8
11.0
15.0
23.0
200°C @
400°C @
0.7
20.0
3.4
5.5
8.0
10.0
16.5
29 bar g
20 bar g
0°C
12.0
2.0
3.4
5.0
6.5
10.0
60barg
60barg
30barg
49barg
0.6
Caution: The trap in its complete operational form must not be subjected to a pressure of greater than 48 bar otherwise damage to the
internal mechanism may result.
Page 2 of 5
TI-P148-04 ST Issue 9
T
e
m
p
e
r
a
t
u
r
e
°
C
T
e
m
p
e
r
a
t
u
r
e
°
C