Technical data
Return flow temperature maintenance with actuator - DN 32 (1
1⁄4")
Application range
● for heating installations with return flow temperature maintenance
● for solid fuel boilers, wood-fired and stove heating systems
Recommended application range
Equipment
Actuator
Electrical data
Power consumption
Torque
Setting time 90°
Materials
Valves and fittings
Gaskets
Insulation
with actuator
230 V / 50 Hz
50 W
5 Nm
140 s
Brass
AFM 34
EPP
● up to 50 W
● 10 K up to 4310 l/h
Operating data
Max. operating pressure
Operating temperature
Kvs value
Dimensions
Nominal diameter
Connection generator
Connection consumer
Installation height
Installation length
6 bar
110 °C
16
DN 32 (1
1⁄4")
11⁄4" int. thread
11⁄4" int. thread
217 mm
497 mm
Grundfos ALPHA2.1 32-60
Grundfos UPM3 Auto L 32-70
Grundfos UPML 32-105 AUTO
Wilo Para SC 30/6-43
Wilo Yonos PICO 30/1-6
Wilo Yonos MAXO plus 30/0.5-10
EEI*
< 0.20
< 0.20
< 0.23
< 0.20
< 0.20
< 0.20
Item no.
960851GH6
960851GM6
960851GL9
960851WP6
960851WN06
960851WY10
* EEI = Energy Efficiency Index