3.1.0.3 MINIMUM CLEARANCES FROM OBJECTS AND OTHER UNITS

• The appliance may be installed in a high or low position.

• Ensure there are no cables, pipes, steel bars or other obstacles

in the wall

.

• Leave at least 10 cm of space to the left, right and from the

fl oor

.

• Leave at least 20 cm of space above the unit to ensure regular

air

fl ow

.

3.2 PERIMETER WALL DRILLING

MOKA units are supplied with a paper template fo

r

marking the holes required for installation

.

Fix the supplied paper template in position on th

e

wall, ensuring that the reference line is horizonta

l

using a spirit level.

Use a 180 mm core drill to drill the two holes for the

unit air intakes, ensuring that both holes are aligned

with the template and maintaining an inclination of a

t

least 5° downwards towards the outside.

Drill the marked holes using a suitable 8 mm drill bi

t

and insert the wall plugs. Align the support bracket

with the holes and secure it in position using th

e

supplied screws.

Ensure that the bracket is securely fixed to the wall

and that there is no risk of the unit overturning o

r

falling

.

Use a 20 mm drill bit for the condensate drain pipe

hole. Ensure that the hole slopes downwards by a

t

least 5°.

Position the metal support on a level

surface capable of supporting its weight

.

3.3 POSITIONING OF THE DUCTS

Measure the depth of the holes drilled in the wall

.

Subtract approximately 5 mm from the measuremen

t

obtained

.

Cut the supplied plastic sheets to size (subtractin

g

the 5 mm)

.

Roll up the plastic sheet

.

Insert the rolled-up sheet into the hole

.

Position so that the edge is recessed into the hole by

approximately 2 mm at both ends

.

No bends are permitted

.

Maximum hole length 1 m.

35