Pipeline ancillaries

HVB3aslltvoaplveaslve

7.4.99

Dimensions/weights (approximate) in mm and kg

PN40 DIN 3202 F4 flanges

Size

A

B

C

D

E

F Weight

PN40 BS 2080 flanges

Size

A

B

C

D

E

F Weight

DN15

-

-

-

-

-

-

-

DN20

-

-

-

-

-

-

-

DN15

115

57

DN20

120

60

DN25

125

62

DN32

130

65

DN40

140

70

DN50

150

75

DN65

170

79

DN80

180

91

DN100 190

98

162

95

95

162

105

95

162

115

101

182

140

106

186

150

118

186

165

123

278

185

144

417

200

157

517

235

172

13

2.5

13

3.2

19

4.0

25

5.5

30

6.9

37

9.3

50

13.4

57

17.7

75

25.0

DN25

165

DN32

178

DN40

190

DN50

216

DN65

241

DN80

283

DN100 305

DN150 403

62

162

115

65

182

140

70

186

150

75

186

165

79

278

185

91

417

200

98

517

235

130

700

300

101

19

4.2

106

25

5.9

118

30

7.4

123

37

10.2

144

50

14.9

157

57

20.2

172

75

29.4

205

100

56.9

DN150

-

-

-

-

-

-

-

B

C

B

C

E

ØD

ØF

Ød

ØF

E

DN15 to DN50

DN65 to DN150

a

Kv values

DN

Kv

For conversion

a

15

20

25

32

40

50

65

80

100

150

10

10

30

40

81

103

197

248

581

735

Cv (UK) = Kv x 0.963

Cv (US) = Kv x 1.156

Operating torque (N m)

DN

15

20

25

32

40

50

65

80

100

150

Nm

8

8

10

15

20

25

80

70

100

155

Note: The torque figures shown are for a valve that is frequently operated at the maximum operating pressure. Valves that are subject to

long static periods, may require a greater break-out torque.

Safety information, installation and maintenance

For full details see the Installation and Maintenance Instructions supplied with the product.

Welding

Only the models that have connections designed for welding (SW, BW, Imperial Tube connections) should be welded. Valves with flanged

connections must not be welded to avoid damages to the valve and/or injury to personnel.

How to order

Model

Seat material

F = Carbon and graphite reinforced PTFE - PDR 0.8

Specify

Material

Body material

2 = Zinc plated carbon steel

3 = Stainless steel

Example: 1 off Spirax Sarco DN50 M21Fi2 ISO ball valve having flanged EN 1092 PN40 connections. Face-to-face according to BS 2080.

Optional extras:

-

Self-venting ball.

-

Extended stems to allow full insulation: 50 mm (2") for DN15 to DN50 sizes and 100 mm (4") for DN15 to DN150 sizes.

-

Lockable handle.

-

100 mm extended stem with lockable handle.

Page 4 of 6

TI-P133-81 ST Issue 4

M21Fi ISO Reduced Bore Firesafe API607 Ball Valve DN15 to DN150 Flanged PN40