Size
DN15
DN20
DN25
DN32
DN40
DN50
DN65
DN80 DN100 DN125 DN150 DN200 DN250
(1⁄2")
(3⁄4")
(1")
(11⁄4")
(11⁄2")
(2")
(21⁄2")
(3")
(4")
(5")
(6")
(8")
(10")
Kv
4
7
12
19
30
47
77
120
193
288
410
725
1145
Size
DN15 DN20 DN25 DN32 DN40
DN50
DN65
DN80
DN100 DN125 DN150 DN200 DN250
Hand-
wheel
rotations
Kv values for given handwheel rotations tested to EN 60534-2-3
Water at 20°C
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.5
1.2
1.2
1.4
2.2
4.4
4.1
5.6
10.4
12.0
21
28
66
110
1
1.7
1.7
2.0
3.7
5.0
5.0
7.0
11.5
14.3
23
30
81
140
1.5
2.7
2.9
2.9
5.0
5.5
6.0
9.2
13.6
24.5
26
33
97
150
2
3.6
4.0
4.6
7.9
7.6
7.2
11.6
16.3
34.1
42
46
111
165
2.5
4.4
5.3
6.4
10.6
11.0
9.7
12.4
18.5
59.6
67
65
149
190
3
5.4
6.6
8.5
13.8
14.7
14.1
13.0
21.1
86.2
94
90
199
225
4
10.6
17.0
22.6
24.4
25.2
24.5
123.0
140
152
302
330
4.5
11.2
18.3
24.4
29.4
32.5
29.0
139.0
181
177
355
451
5
11.9
19.6
27.2
37.0
43.6
39.1
164.1
185
216
403
460
6
28.9
46.2
60.2
61.0
179.0
220
264
455
600
6.5
29.1
47.0
63.0
69.0
186.0
230
288
480
641
6.7
29.3
47.2
64.3
73.0
235
293
487
656
7
65.9
78.0
241
305
495
678
8
71.2
90.0
259
337
507
738
8.5
74.6
92.0
348
522
760
9.5
99.0
369
793
10
101.6
805
10.7
827
DN15 -DN80
2.0bar
DN100 - DN125
1.5 bar
DN150
1.0 bar
DN200 - DN250
0.8 bar
Disc to seat shut-off conforms to EN 12266-1 Rate A leakage and ISO 5208 Rate A. Disc to seat shut-off for BSA3 (ANSI) conforms to
API 598 no leakage.
For conversion:
Cv (UK) = Kv x 0.963
Cv (US) = Kv x 1.156
Note: For Kv values and flow characteristic values of the BSA1T, BSA2T and BSA3T see the next section 'BSAT flow data'.
= Kv x √ ∆P
Where:
= Volume flow in cubic m/h
∆P = Pressure drop in bar
Note: The maximum recommended differential pressure in
throttling function:
If the BSAT is used above these quoted figures, increased noise
and vibration may be experienced.
Handwheel rotations
Handwheel rotations
Page 4 of 10
K
v
r
v
a
l
u
e
s
K
v
r
v
a
l
u
e
s