Model
Connections
Motor
Vessel inlet
Discharge
Vent
Overflow
outlet
Dry
Weight (kg)
Wet
SPM202-1 0.55 DN40 BSP DN25 BSP DN50 BSP DN40 BSP 54 184
SPM203-1 0.55 DN40 BSP DN25 BSP DN50 BSP DN40 BSP 54 184
150
150
6
6
4
488
438
2
1
3
50
500
1 000
440
50
Nozzle Schedule (BSP)
7
5
170
5
1. Condensate inlet 11⁄2" BSP
2. Open vent 2" BSP
3. Over flow 11⁄2" BSP
4. Pump discharge
5. Vessel downpipe 35 mm
6. Level probe x 1" BSP (Bush to 1⁄2")
7. Tank drain 1⁄2" BSP (c/w plug)
Ø475
338 388
Information required for sizing and selection:
1. Average rate at which condensate returns to the receiver in kg/h.
2. Total pumping delivery head, including lift and friction loss in pipe and fittings.
Sizing and selection
For correct selection plot the condensate return rate to be handled against the total head required (static + friction) and select the appropriate
unit. If selection is borderline then select the next largest unit.
Selection example: The condensate return rate is known to be
����
1200 kg/h and the total head required is 25 m. Draw a horizontal
line from the known 25 m head required until it crosses the vertical
line which represents the known 1200kg/h condensate which
needs to be handled. For this example the selection would be an
SPM203-1 condensate recovery unit.
The condensate recovery unit shall be a Spirax Sarco compact SPM
condensate recovery unit type SPM203-1 designed and built to
handle 1200kg/h of condensate against a required head of 25 m.
��������
��������
����
����
����
����
Example: 1 off SPM203-1 condensate recovery unit.
���
�
���
����
����
����
Condensate to be handled at 98°C kg/h
SPM Stainless Steel Condensate Recovery Units
TI-P089-38 ST Issue 2