EKO-CUPS3
125
160
240
320
400
460
530
600
(kW)
37,5-125
48-160
72-240
96-320
120-400
138-460
168-530
180-600
Heatoutput
Boiler water content
Total boiler mass
Max. operating temperature
Max. operating overpressure / flanges
(mm)
Ø (mm)
Combustion chamber resistance (mbar)
200/790
250/890
170
170
2,6
2,8
250/970
250/970
300/1062
300/1062
170
220
220
220
3,5
4,0
4,3
4,9
Flue gas tube diameter * / height (I)
Burner opening
(l)
(kg)
(°C)
225
290
445
563
90/100/105 90/100/105
180/700
200/790
130
130
1,7
2,5
390
465
615
673
867
1066
90/100/105 90/100/105 90/100/105
3 bar / NP6 ili 6 bar / NP16
735
865
970
1184
1418
1515
90/100/105 90/100/105 90/100/105
Mainflow/returnflow
Filling / draining
(R)
Safetyline
(R)
1"
1"
5/4"
6/4"
6/4"
6/4"
140
140
140
1890
1945
2245
1050
1150
1150
1225
1355
1355
1930
1985
2285
1050
1150
1150
1320
1420
1420
1150
1250
1250
440/175
450/185
450/185
6/4"
6/4"
140
140
2245
2495
1250
1250
1460
1455
2285
2530
1250
1250
1520
1520
1350
1350
475/185
480/185
Flue gas temperature
Boiler body length A
Boiler body width B
Boiler body height C
Total length D
Total width E
Total height F
Height G
Heights (H / K)
(°C)
140
(mm)
1630
(mm)
780
(mm)
970
(mm)
1660
(mm)
780
(mm)
1080
(mm)
910
(mm)
360/175
140
140
1475
1890
945
945
1110
1110
1510
1930
945
945
1210
1210
1040
1040
440/175
440/175
R2"
DN50
DN65
DN80
DN80
DN80
DN80
DN100
3/4"
3/4"
3/4"
3/4"
1"
1"
1"
1"
* The inner diameter of the chimney is determined according to the power of the boiler and the height of the chimney and must almost always be larger than the diameter of the flue gas tube