General conditions
Appearance
Total hardness
pH
Electrical conductivity
Chlorides
The water must comply with the requirements for the water intended to human consumption
by current legislation Decree 31/2001.
Limpid
System capacity ≤ 100 kW: no limit
System capacity > 100 kW: between 5 and 15 °f
Between 6.5 and 9.5
Plant capacity> 100 kW: <1500 μS / cm at 20 °C
With concentrations higherr than 50 mg / lt and in the presence
of steel equipment molybdenum-free stainless steel, check the suitability
of the systems with manufacturer.
CIRCUIT - Paragraph 7.2.4
Appearance
pH
Conditioners•
Iron (as Fe)
Copper (like Cu)
Aluminum (as Al)
Chlorides
Limpid
In absence of aluminum and its alloys: between 6.5 and 9.5
In the presence of aluminum and its alloys: between 7 and 8.5
must be present in the concentrations prescribed by the supplier in relation
to the performance required in terms of antiscaling, anticorrosive properties,
biocides and antifreeze.
<0.5 mg / lt (higher iron values are due to corrosive phenomena to be eliminated)
<0.1 mg / lt (higher copper values are due to corrosive phenomena to be eliminated)
<0.1 mg / lt (higher aluminum values are due to corrosive phenomena to be eliminated)
With concentrations higher than 50 mg / lt and in the presence of steel equipment
stainless steel free of molybdenum, check with the manufacturer
of the equipment the suitability of the product.
Go to the PRODUCT page of
T.EM.I.T. LINE Treatment and maintenance of Thermal plants
Let’s follow step by step the 6 key points of the Standard, which has the following aim:
Go to the depth analisis
performance and safety, to preserve them over time, to ensure long-lasting regularity of operation even to auxiliary
equipment and to minimize energy consumption thus integrating laws and standards in force.
Where to turn?
Through the Facot Chemicals and in particular the Check Service analysis service, available from the best national whole-
salers-distributors, and the Facot Service assistance centers, it will be possible to check the , chemical-physical parameters
and have all the technical support necessary for the efficiency of the installations.
Let’s analyze the water characteristics of:
FILLING AND RE-INTEGRATION - Paragraph 7.2.3