Dimensions / weights (approximate) in mm and kg

Capacities

�� ������

�� ������

�� ������

�� ������

��������

������

������

������

������

������

������

�����������

������

��

������

��������

Weight

D

E BPT13T BPT13TGX

50 55

1.1

1.35

50 55

1.2

1.45

50 55

1.5

1.75

E Withdrawal distance

B

D

C

The trap is designed for installation with the capsule in a horizontal

plane and the cap at the top, preferably with a drop leg immediately

preceding the trap. See IM-P126-05 for full installation details.

Warning:

Under certain conditions corrosive elements in condensate

can effect the inside face of the sight tube, particularly where

caustic alkali and hydrofluoric acid are present. It is

recommended that the sight tube is periodically checked for

thinning. If there is evidence of thinning or erosion damage

then the sight tube should be replaced immediately. Always

wear eye protection when viewing the contents of the

sight tube.

Reasonable steps should be taken to protect personnel from

injury in the unlikely event that the sight tube breaks.

Operation

The trap is supplied in the 'Bypass' position (1). To move it to

'Trap' (2) or 'Stop' (3) position the actuator should be moved until

the indicator aligns with the marking on the body.

1

2

3

Maintenance

See IM-P126-05 for full maintenance details

Before any maintenance is undertaken, suitable independent isolation

valves should be closed and the trap positioned in the 'bypass' mode.

Allow the trap to cool. Remove the cap and lift out the old capsule,

spring and spacer plate. Drop in a new spacer plate,

capsule and spring. Screw on the cap using a new 'O' ring assembled

into the groove in the top of the cap. Always fit a completely new

assembly when replacing the capsule.

Recommended tightening torques

Size

A

B B1 C

1⁄2"

92 97 133 45

3⁄4"

92 117 153 45

1"

92 127 163 45

A

Indicator

Installation

Hot water capacity

The spare parts available are shown in heavy outline. Parts drawn

in broken line are not supplied as spares.

Available spares

Capsule assembly

Maintenance kit

Sight tube assembly

Replacement of capsule assembly:

BPT13T

3

19

18

17

16

12

15

11

6

13 14

6

7

4

Item

2 and 20

2 and 20

2 and 20

3

4

7

9

12

Size

DN15

32

DN20

36

DN25

46

or

Nm

mm

35 - 40

35 - 40

35 - 40

50 - 60

-

7 - 10

12 - 15

12 - 15

20

Sight tube

assembly

21 22 21

2

DN15 - 25

DN15 - 25

DN15 - 25

DN15 - 25

DN15 - 25

50

30

13

13

17

B1

How to order

Example: 1 off 1⁄2" Spirax Sarco BPT13 balanced pressure

thermostatic steam trap with a capsule marked 'SUB' for

sub-cooled operation.

Steam traps

Balanced pressure

C

a

p

a

c

i

t

i

e

s

k

g

/

h

9

TI-P126-03 ST Issue 6

BPT13T and BPT13TGX Thermostatic Steam Traps

Spare parts

2

14 13

Differential pressure bar (x 100 = kPa)

Cold water capacity

16, 17*, 18, 19

6 (2 off), 11, 12, 13 (2 off), 14 (2 off),

*Note: The capsule can be identified from the letter stamped on

the name-plate on the cap (e.g. STD, SUB or NTS). A standard

capsule (STD) will be supplied, unless specified otherwise on

the order.

Always order spares by using the description given in the column

headed 'Available spares' and state the size and type of trap.

Example: 1 - Capsule assembly, marked STD, for a Spirax Sarco

BPT13T balanced pressure thermostatic steam trap.

How to order spares

BPT13GX only

15, 16, 17*, 18, 19

21 (2 off), 22

5.2.4