Minimum pulse width

Boiler house

Energy monitor

PULS type inputs (binary / pulse / frequency)

Measuring range

0 .. 20 kHz (cut off for f < 0.001 Hz)

(0 ..1 kHz with filter jumper J1 / J2 / J3 ON)

25 μs (0.5 ms with filter jumper J1 / J2 / J3 ON)

Accuracy for frequency measurement

(at T

amb

= +25 °C / +77 °F)

0.02%

Maximum input voltage

±40 Vdc / SELV

Galvanic isolation between inputs

No; common potential of functional GND for all inputs

Galvanic isolation to Analog Outputs, RS-485 / RS-422, Ethernet

250 Vac continuous; 1500 Vac for 1 minute

Configuration (default): OC or Contact open / closed

(Internal jumper J4 / J5 / J6 ON)

Open circuit voltage

5 Vdc

Short circuit current

5 mA

On / off threshold

2.7V / 2.4V

2.12.6

Configuration: Voltage Input

(Internal jumper J4 / J5 / J6 OFF)

Signal amplitude

4 .. 36 Vdc

On / off threshold

2.7V / 2.4V

Input resistance

≥10 kW

Compensated flow and heat energy measurement

Calculation update rate

1s

Total accuracy of compensated steam, water, other liquid or

technical gas flow measurement

Typical: better then ± 0.5% (worst case: better then ± 2%)

4-20 mA analog outputs

Number of outputs

2

Output signal

Resolution

4 - 20 mA passive (external current loop supply required)

16 bit DAC

Loop resistance (R

L

) range for U

CC

= 24 V

0 .. 600 Ω

Minimum loop power supply voltage

U

CCmin

=RLx0.022+8

Maximum loop power supply voltage

28 Vdc / SELV

Accuracy (at T

amb

= +25 °C / +77 °F)

Better than ± 0.2% of FS / °C

Temperature drift

Maximum ± 0.02% of FS / °C

Galvanic isolation to Analog Inputs, RS-485 / RS-422, Ethernet

250 Vac continuous; 1500 Vac for 1 minute

Binary outputs (B850-W-2 and B850-W-2-UL)

Number of outputs

4

Type of outputs

3 pole (COM, NO, NC) electromechanical relay

Contact rating (resistive load)

3Aat85..250Vac / 30Vdc

Maximum switching voltage

250 Vac / 125 Vdc

Maximum switching power

750VA / 90W

Binary outputs (B850-P-2)

Number of outputs

4

Type of outputs

2 pole Solid State Relay

Contact rating (resistive load)

Maximum ON resistance

0.1 A at 24 Vac/dc (max 42 Vac 60 Vdc) / SELV

20 Ω

Galvanic isolation (optoisolation)

250 Vac continuous; 1500 Vac for 1 minute

TI-P408-01 EMM Issue 5

Page 5 of 8

B850 Boiler House Energy Monitor