Minimum pulse width
Measuring range
0 .. 20 kHz (cut off for f < 0.001 Hz)
(0 ..1 kHz with filter jumper J1 / J2 / J3 ON)
25 μs (0.5 ms with filter jumper J1 / J2 / J3 ON)
Accuracy for frequency measurement
(at T
amb
= +25 °C / +77 °F)
0.02%
Maximum input voltage
±40 Vdc / SELV
Galvanic isolation between inputs
No; common potential of functional GND for all inputs
Galvanic isolation to Analog Outputs, RS-485 / RS-422, Ethernet
250 Vac continuous; 1500 Vac for 1 minute
Configuration (default): OC or Contact open / closed
(Internal jumper J4 / J5 / J6 ON)
Open circuit voltage
5 Vdc
Short circuit current
5 mA
On / off threshold
2.7V / 2.4V
Configuration: Voltage Input
(Internal jumper J4 / J5 / J6 OFF)
Signal amplitude
4 .. 36 Vdc
On / off threshold
2.7V / 2.4V
Input resistance
≥10 kW
Calculation update rate
1s
Total accuracy of compensated steam, water, other liquid or
technical gas flow measurement
Typical: better then ± 0.5% (worst case: better then ± 2%)
Number of outputs
2
Output signal
Resolution
4 - 20 mA passive (external current loop supply required)
16 bit DAC
Loop resistance (R
L
) range for U
CC
= 24 V
0 .. 600 Ω
Minimum loop power supply voltage
U
CCmin
=RLx0.022+8
Maximum loop power supply voltage
28 Vdc / SELV
Accuracy (at T
amb
= +25 °C / +77 °F)
Better than ± 0.2% of FS / °C
Temperature drift
Maximum ± 0.02% of FS / °C
Galvanic isolation to Analog Inputs, RS-485 / RS-422, Ethernet
250 Vac continuous; 1500 Vac for 1 minute
Number of outputs
4
Type of outputs
3 pole (COM, NO, NC) electromechanical relay
Contact rating (resistive load)
3Aat85..250Vac / 30Vdc
Maximum switching voltage
250 Vac / 125 Vdc
Maximum switching power
750VA / 90W
Number of outputs
4
Type of outputs
2 pole Solid State Relay
Contact rating (resistive load)
Maximum ON resistance
0.1 A at 24 Vac/dc (max 42 Vac 60 Vdc) / SELV
20 Ω
Galvanic isolation (optoisolation)
250 Vac continuous; 1500 Vac for 1 minute
TI-P408-01 EMM Issue 5
Page 5 of 8