Pressure psi g
A
N
M
Steam
saturation
Pressure bar g
curve
N
O
M
The product must not be used in this region.
An extended cover is required for use in this region.
High temperature packing required for use in this region.
Notes:
1. Where the process fluid temperature is sub-zero and the ambient temperature is below +5 °C, the external moving parts of the valve
and actuator must be heat traced to maintain normal operation.
2. When selecting a valve with a bellows scaled bonnet, the pressure / temperature limits of the bellows must be read in conjunction with
the valve pressure / temperature limits shown in table below.
Body design conditions
PMA Maximum allowable pressure
and
99.3barg@38°C
PMO Maximum operating pressure
ASME 600
1440 psi g @ 100 °F
1000 °F @ 725 psi g
-20 °F
482 °F @ 967 psi g
1000 °F @ 725 psi g
-20 °F
2 262 psi g
ASME 300
1440 psi g @ 100 °F
1000 °F @ 365 psi g
-20 °F
482 °F @ 484 psi g
1000 °F @ 365 psi g
-20 °F
1 087 psi g
ASME 150
275 psi g @ 100 °F
1000 °F @ 20 psi g
-20 °F
482 °F @ 175 psi g
1000 °F @ 20 psi g
-20 °F
2 262 psi g
Page 9 of 17
A-M-M
A-N-N
A-O
TMA Maximum allowable temperature
Minimum allowable temperature
TMO Maximum operating
Standard packing PTFE chevron (P)
538 °C @ 50 bar g
-29 °C
250 °C @ 66.8 bar g
538 °C @ 50 bar g
-29 °C
156 bar g
temperature
High temperature packing (H)
Minimum operating temperature
Design for a maximum cold hydraulic test pressure
of:
Body design conditions
PMA Maximum allowable pressure
and
49.6barg@38°C
PMO Maximum operating pressure
TMA Maximum allowable temperature
Minimum allowable temperature
TMO Maximum operating
Standard packing PTFE chevron (P)
538 °C @ 25.2 bar g
-29 °C
250 °C @ 33.4 bar g
538 °C @ 25.2 bar g
-29 °C
75 bar g
temperature
High temperature packing (H)
Minimum operating temperature
Design for a maximum cold hydraulic test pressure of:
Body design conditions
PMA Maximum allowable pressure
and
19barg@38°C
PMO Maximum operating pressure
TMA Maximum allowable temperature
Minimum allowable temperature
TMO Maximum operating
Standard packing PTFE chevron (P)
538 °C @ 1.4 bar g
-29 °C
250 °C @ 12.1 bar g
538 °C @ 1.4 bar g
-29 °C
29 bar g
temperature
High temperature packing (H)
Minimum operating temperature
Design for a maximum cold hydraulic test pressure of:
TI-P405-51 AB Issue 1
T
e
m
p
e
r
a
t
u
r
e
°
F
T
e
m
p
e
r
a
t
u
r
e
°
C