Pipeline ancillaries

Sight glasses

Dimensions / weights (approximate) in mm and kg

Single window

Size A

B

C

D

E

F

Weight

Spare parts

The spare parts available are shown in heavy outline. Parts drawn

in broken line are not supplied as spares.

3

/

8

"

89

16

32

64

50

4.8

64

50

4.8

64

50

4.8

64

50

4.8

0.6

0.6

0.7

0.9

Available spares

Set of windows and gaskets

Set of gaskets

Always order spares by using the description given in the

column headed 'Available spares' and state the size and type of

sight glass.

Example: 1 off Set of windows and gaskets for a 1" Spirax Sarco

double window sight glass.

1⁄2"

89

3⁄4"

89

1"

87.5

F

16

32

19

35

24

38

3, 4, 5

4, 5

How to order spares

C

B

Single window

2

A

Size A

B

C

D

E

F

Weight

4

3

5

Double window

1⁄2"

89

-

32

-

32

-

35

-

51

-

51

-

57

64

50

4.8

64

50

4.8

64

50

4.8

73

50

4.8

73

50

4.8

76

50

4.8

0.9

0.9

1.2

1.9

1.8

2.5

3⁄4"

89

1"

89

11⁄4" 108

11⁄2" 108

2"

114

F

Double window

Ensure access is available for maintenance purposes.

Disposal

Recommended tightening torque

D

E

A

D

The product is recyclable. No ecological hazard is anticipated with

disposal of this product providing due care is taken.

How to order

Example: 1 off Spirax Sarco 1" BSP double window sight glass with

brass body and removable toughened soda lime glass.

Item No.

2

Part

Bezel

C

2

C

4

3

5

E

Safety information, installation and maintenance

For full details see the Installation and Maintenance Instructions

(IM-S32-04) supplied with the product.

Warning:

Under certain conditions corrosive elements in condensate can

affect the inside face of the window(s), particularly where caustic

alkali and hydrofluoric acid are present. It is recommended that the

sight glass is periodically checked for thinning of the window(s). If

there is evidence of thinning or erosion damage then the window(s)

should be replaced immediately. Always wear eye protection when

viewing the contents of the sight glass.

Sight glasses should have stop valves fitted on both the inlet and

outlet. It is imperative that the upstream stop valve is closed first in

order to prevent overpressurisation.

Sight glasses can be fitted in either a horizontal or vertical line on

the outlet side of a steam trap. Where the trap is a blast discharge

type e.g. thermodynamic, the sight glass must be fitted at least

1 m from the trap. This is to ensure that the glass is not subjected

to thermal shock or pressure. Reasonable steps should be taken

to protect personnel from injury in the unlikely event that the glass

breaks.

Installation and maintenance note:

5

3

4

N m

60 - 65

TI-P022-05 ST Issue 4

or

mm

Single Window and Double Window Sight Glasses

7.9.2