Page 5 of 8
A
D
Steam
saturation
curve
H
C
B
G
E
Steam
saturation
curve
F
A -B
A -C
D- G
D- H
Screwed BSP and flanged EN
Screwed NPT and flanged EN
Flanged ASME 250.
Flanged ASME 125.
1092 PN25.
1092 PN16.
Pressure bar g
The product must not be used in this region.
E - F
Pressure bar g
The product must not be used in this region.
Flanged JIS / KS 10.
Body design conditions
PMA Maximum allowable pressure
TMA Maximum allowable temperature
Minimum allowable temperature
PN16
16 bar g @ 120°C
300°C @ 12.8 bar g
-10°C
14.7 bar g
300°C @ 12.8 bar g
-10°C
24 bar g
PN25
25 bar g @ 120°C
300°C @ 20 bar g
-10°C
22.5 bar g
300°C @ 20 bar g
-10°C
38 bar g
ASME 125
13.8 bar g @ 65°C
232°C @ 8.6 bar g
-10°C
10 bar g
232°C @ 8.6 bar g
-10°C
20.5 bar g
ASME 250
34.5 bar g @ 65°C
232°C @ 17.2 bar g
-10°C
19.4 bar g
232°C @ 17.2 bar g
-10°C
52 bar g
JIS / KS 10
13.7 bar g @ 120°C
300°C @ 9.8 bar g
0°C
12.3 bar g
300°C @ 9.8 bar g
0°C
20 bar g
Flanged EN 1092 PN16
PMO Maximum operating pressure for saturated steam service
TMO Maximum operating temperature
Screwed BSP
and
Flanged EN 1092 PN25
Minimum operating temperature
Note: For lower operating temperatures consult Spirax Sarco.
Designed for a maximum cold hydraulic test pressure of:
Body design conditions
PMA Maximum allowable pressure
TMA Maximum allowable temperature
Minimum allowable temperature
PMO Maximum operating pressure for saturated steam service
TMO Maximum operating temperature
Minimum operating temperature
Note: For lower operating temperatures consult Spirax Sarco.
Designed for a maximum cold hydraulic test pressure of:
Body design conditions
PMA Maximum allowable pressure
TMA Maximum allowable temperature
Minimum allowable temperature
Flanged ASME 125
PMO Maximum operating pressure for saturated steam service
TMO Maximum operating temperature
Minimum operating temperature
Note: For lower operating temperatures consult Spirax Sarco.
Designed for a maximum cold hydraulic test pressure of:
Body design conditions
PMA Maximum allowable pressure
TMA Maximum allowable temperature
Screwed NPT
and
PMO Maximum operating pressure for saturated steam service
Flanged ASME 250
TMO Maximum operating temperature
Minimum operating temperature
Note: For lower operating temperatures consult Spirax Sarco.
Designed for a maximum cold hydraulic test pressure of:
Body design conditions
PMA Maximum allowable pressure
TMA Maximum allowable temperature
Minimum allowable temperature
Minimum allowable temperature
Flanged JIS / KS 10
PMO Maximum operating pressure for saturated steam service
TMO Maximum operating temperature
Minimum operating temperature
Note: For lower operating temperatures consult Spirax Sarco.
Designed for a maximum cold hydraulic test pressure of:
LCV3, LCV4, LCV6 and LCV7 Lift Check Valves
TI-P029-16 ST Issue 4
Page 5 of 8
T
e
m
p
e
r
a
t
u
r
e
°
C
T
e
m
p
e
r
a
t
u
r
e
°
C