Boiler house

TDS blowdown controls

2.4.13

Pressure / temperature limits – BCV7_

Body design conditions:

PN25

JIS/KS 10K

25.0barg@120°C

11.5barg@140°C

26.7barg@140°C

13.7barg@120°C

300°C@20barg

232°C@ 8.6barg

232°C@17.2barg

300°C@ 9.8barg

-10 °C

-29 °C

-29 °C

-10 °C

22.5barg@220°C

10.0barg@184°C

18.0barg@209°C

12.3barg@191°C

300°C@20.0barg

232°C@ 8.6barg

232°C@17.2barg

300°C@ 9.8barg

-10 °C

-29 °C

-29 °C

-10 °C

ASME class 125 or

ASME class 250

166psig@284°F

387psig@284°F

449°F@125psig

449°F@249psig

-20 °F

-20 °F

145psig @363°F

261psig@408°F

449°F@125psig

449°F@249psig

-20 °F

-20 °F

EN

PN25

ASME 125

ASME 250

JIS/KS10K

PN25

ASME 125

ASME 250

JIS/KS10K

PN25

ASME 125

ASME 250

JIS/KS10K

PN25

ASME 125

ASME 250

JIS/KS10K

PN25

ASME 125

ASME 250

JIS/KS10K

PN25

ASME 125

ASME 250

JIS/KS10K

PMA Maximum allowable pressure

ASME

JIS/KS

EN

TMA Maximum allowable temperature

ASME

JIS/KS

EN

Minimum allowable temperature

ASME

JIS/KS

EN

PMO

Maximum operating pressure for

ASME

saturated steam service

JIS/KS

EN

TMO Maximum operating temperature

ASME

JIS/KS

EN

Minimum operating temperature

ASME

JIS/KS

Designed for a maximum cold hydraulic test pressure of:

1.5 x PMA of the relative end connection of choice

Page 8 of 14

TI-P403-102 AB Issue 4

BCV Blowdown Control Valves DN15 to DN50 (1⁄2" to 2")