Characteristics of boilers EKO-CUP V3 / SV3
— Hot water boiler for central heating with three-pass flue gas system,
— The maximum operating overpressure of the boiler is 6 bar, which allows installation in central heating systems of tall buildings.
— The maximum operating temperature of the EKO-CUP V3 boiler is 105°C, while the maximum operating
temperature of the EKO-CUP SV3 boiler is 100°C.
— Built-in spiral turbulators enable better heat transfer from flue gases to boiler water, regulation of furnace resistance,
regulation of flue gas outlet temperature, i.e. quality coordination of boiler-burner-chimney operation.
— A lot of water in the boiler reduces the number of starts and prolongs the life of the burner and saves energy.
— The technical solutions used are the reason for the almost negligible initial condensation.
— All boiler connections are on the top, which allows easy connection to the installation.
— Boiler door with blind plate is adapted for the installation of all fan burners on the market and can be opened to the left
and right by 90°, which allows easy and quick cleaning of the boiler.
— Deliveryoftheboiler:separateboilerbody,separatecasingwiththermalinsulationwhichenableseasytransportandinstallationof
the boiler, and separately selected controller.
EKO-CUP S3 / V3-REG / 90°C
— The basic boiler controller (with EKO-CUP V3 and SV3 it is possible to order controller with a maximum boiler operating
burner according to the set boiler water temperature.
— The controller includes a safety and operating thermostat of the first and second stage of the burner and a thermometer.
CUPREG-Touch / 90°C / 100°C / 105°C
— Digital boiler controller (with EKO-CUP V3 it is possible to order controller with a maximum boiler operating temperature
of 90°C, 100°C or 105°C, and with EKO-CUP SV3 with a maximum boiler operating temperature of 90°C and 100°C) can
control the operation of a single-stage, two-stage or modulating oil or gas burner and controls the central heating system
(up to 2 mixing heating circuits controlled by outdoor temperature), the cascade of several boilers and the preparation of
domestic hot water.
— Possibility of remote monitoring and control of the boiler via web portal (requires additional equipment CM- WiFi box), CM2K
module for additional heating circuits, oil level sensor in the tank ...
Boiler cross section
EKO-CUP V3 / SV3 0.8-2.1 MW
Boiler delivery
Boiler connections
Basic boiler
controller EKO-CUP
S3/V3-REG
Digital boiler
controller CUPREG-
Touch