H
e
a
t
B
l
o
C
®
M
C
4
1
D
N
2
5
(
1
"
)
Technical data
Application range
● Boiler charging
● modulating temperature heating system
Operating data
Range of performance
Temperature difference
Kvs value
Max. operating pressure
Operating temperature
up to 50 kW
20 K up to 2150 l/h
7.2
6 bar
110 °C
38
01/2024 • Printed in Germany
PAW GmbH & Co. KG • info@paw.eu • www.paw.eu
Functions
● differential pressure controlled, for the automatic, dynamic balancing of the distribution manifold
● for hydraulic balancing of the radiators, the HeatBloC® MC41 as well as the PAW Connect App are necessary
● the connection of 1-8 controllers to the power supply requires a connection set
● the integration in a Smart Home environment is possible with the MCom communication set (item no.: 1398731)
Equipment
Controller MCom 3.4
Temperature sensors
Differential pressure sensors
Thermometer
Check valves
Materials
Valves and fittings
Gaskets
Insulation
24 Vdc, max. 200 mA
Interface: Modbus RTU (integration
into building control and
SmartHome systems )
1x Pt1000 in the flow and return
0-600 mbar
0 - 120 °C
1 x 200 mm wc
Brass
EPDM
EPP
Dimensions
Nominal diameter
Connection generator
Connection consumer
Height
Installation length
Centre distance
Width
DN 25 (1")
11⁄2" ext. thread, flat sealing
1" int. thread
500 mm
340 mm
125 mm
250 mm