The heating circuits recommended for combination with the system separations (36533, 36553, 36573) are listed on this page. Equipment and prices of the
heating circuits can be found on pages K31, K32 and K34.
Note: the heating circuits have to be ordered seperately. The assembly must be carried out on-site!
Application 1:
Extension of already existing heating circuits / installations with a temperature control on the primary side (mixed heating circuit with controlled
flow
temperature or modulating boiler with boiler circuit pump).
Mounting example
Heating circuit
Pump
EEI*
System separation
Range of performance**
36013WP6
36013GH6
36013GM6
36063WP6
36063GH6
36063GM6
prim. 36053MWP6
sec. 36013WP6
prim. 36053MGH6
sec. 36013GH6
prim. 36053MGM6
sec. 36013GM6
Wilo Para 25/6-43
≤ 0.2
Grundfos ALPHA2.1
25-60
≤0.17
Grundfps UPM3 Auto L
≤ 0.2
25-70 PP3
Wilo Para 25/6-43
≤ 0.2
Grundfos ALPHA2.1
≤0.17
25-60
Grundfos UPM3 Auto L
≤ 0.2
25-70 PP3
Wilo Para 25/6-43
≤ 0.2
Grundfos ALPHA2.1
25-60
36533
36553
36573
36533
36553
36573
36533
36553
36533
36553
36573
36533
36553
36573
36533
36553
36533
36553
36533
36553
36533
36553
1580 l/h = 18.3 kW
1830 l/h = 21.2 kW
1930 l/h = 22.4 kW
1480 l/h = 17.2 kW
1710 l/h = 19.9 kW
1790 l/h = 20.8 kW
1720 l/h = 20.0 kW
2020 l/h = 23.5 kW
1540 l/h = 17.9 kW
1780 l/h = 20.7 kW
1860 l/h = 21.6 kW
1450 l/h = 16.8 kW
1650 l/h = 19.2 kW
1730 l/h = 20.1 kW
1690 l/h = 19.6 kW
1950 l/h = 22.6 kW
1540 l/h = 17.9 kW
1750 l/h = 20.3 kW
1440 l/h = 16.7 kW
1630 l/h = 18.9 kW
1670 l/h = 19.4 kW
1930 l/h = 22.4 kW
36573
2120 l/h = 24.6 kW
Application 2:
Extension of already existing heating circuits / installations with a pump on the primary side and high
flow temperatures (bypass operation in addition to
the radiator circuits or operation with solid fuel boiler and boiler circuit pump).
Mounting example
Heating circuit
Pump
EEI*
System separation
Range of performance**
36573
2030 l/h = 23.6 kW
Application 3:
Complete system separation with mixing valve control on the primary side. Ensures low return temperatures of the boiler and allows the operation of
several parallel heating circuits, f. ex. on a distribution manifold.
Mounting example
Heating circuit
Pump
EEI*
System separation
Range of performance**
36573
1830 l/h = 21.2 kW
≤0.17
36573
1710 l/h = 19.9 kW
36573
2000 l/h = 23.2 kW
Grundfps UPM3 Auto L
≤ 0.2
25-70 PP3
** At a primary temperature of 60 - 50 °C, a secondary temperature of 35 - 45 °C and a secondary residual head of 1.5 m wc
01/2024 • Printed in Germany