SATELLITI D’UTENZA - HEAT INTERFACE UNITS (HIU)

Mod. 31000 - NOVAHIU V1

Art. 31000 NOVAHIU V1-13 Basic

7

DATI TECNICI

Portata max.

Temperatura max.

Pressione max.

Valore Kv

1)

Perdite di carico

1) 2)

Liquido

Predisposizione contatore di calore

Scambiatore di calore a piastre

Numero di piastre

Valvola di zona

Tensione di alimentazione

Assorbimento elettrico

Controllo della portata sul primario

Valvola PV (controllo pressione differenziale)

Regolazione

CIRCUITO PRIMARIO

900 lt/h

85 °C

16 bar

1,5

Vedere grafici specifici

2)

Acqua – Acqua + Glicole max. 30%

110 mm – 3/4” M

Zilmet ZB 315 – Fast Connections

13

2 vie – Motore controllato a 3 punti

230 V – 50 Hz

max. 8,5 W

NO

NO

SÌ

SÌ

SÌ

SÌ

TECHNICAL DATA

Max. flow rate

Max. temperature

Max. pressure

Kv value

1)

Pressure losses

1) 2)

Liquid

Heat meter predisposition

Plate heat exchanger

Number of plates

Zone valve

Electricity supply

Electrical absorption

Primary flow rate control

PV valve (differential pressure control)

Setting

PRIMARY CIRCUIT

900 lt/h

85 °C

16 bar

1,5

See specific graphics

2)

Water – Water + Glycol max. 30%

110 mm – 3/4” M

Zilmet ZB 315 – Fast Connections

13

2 way – Motor 3 points controlled

230 V – 50 Hz

max. 8,5 W

NO

NO

YES

Flusso by-pass

Filtro

Sfiato aria

Drenaggio

Portata max.

T emperatura max.

Pressione max.

Prevalenza residua a 1000 lt/h

Prevalenza residua

3)

Potenza termica nominale

4)

Liquido

Circolatore

Regolazione

Tensione di alimentazione

Assorbimento elettrico

Vaso d’espansione

Capacità

Precarica

Valvola termostatica controllo temperatura

Regolazione

Pressostato di minima

Pressione ON

Pressione OFF

Valvola di sicurezza

Regolazione

Manometro

Filtro

Sfiato aria

Drenaggio

Tensione di alimentazione

Consumo energetico

Grado di protezione IP

Flushing by-pass

Strainer

YES

Air purge

YES

Drain

YES

CIRCUITO RISCALDAMENTO APPARTAMENTO

APARTMENT HEATING CIRCUIT

720 lt/h

80 °C

3 bar

35,6 kPa

See specific graphics

3)

16 kW

Water – Water + Glycol max. 30%

Grundfos UPM3 Hybrid 15-70 130

Proportional Curve

230 V – 50 Hz

min. 2 W – max. 52 W

Zilmet 13I0000901

9 lt

1 ± 0,2 bar

NO

YES, ON / OFF

0,35 bar

0,15 bar

YES

3 bar

YES, 0-10 bar

Strainer

YES

720 lt/h

80 °C

3 bar

35,6 kPa

Vedere grafici specifici

3)

16 kW

Acqua – Acqua + Glicole max. 30%

Grundfos UPM3 Hybrid 15-70 130

Curva Proporzionale

230 V – 50 Hz

min. 2 W – max. 52 W

Zilmet 13I0000901

9 lt

1 ± 0,2 bar

NO

SÌ, ON / OFF

0,35 bar

0,15 bar

SÌ

3 bar

SÌ, 0-10 bar

SÌ

SÌ

SÌ

CARATTERISTICHE ELETTRICHE GENERALI

230 V – 50 Hz

max. 60,5 W

IPX0D

CARATTERISTICHE MECCANICHE

Max. flow rate

Max. temperature

Max. pressure

Residual head at 1000 lt/h

Residual head

3)

Nominal heating power

4)

Liquid

Pump

Setting

Electricity supply

Electrical absorption

Expansion vessel

Capacity

GENERAL ELECTRICAL CHARACTERISTICS

230 V – 50 Hz

max. 60,5 W

IPX0D

MECHANICAL CHARACTERISTICS

3/4” M

3/4” M

70 mm

3/4” M

3/4” M

140 mm

Copper pipe Ø15 mm

1/2” M

550 x 450 x 240 mm

21,5 kg

21,0 kg

Precharge

Thermostatic temperature control valve

Setting

Minimum pressure switch

Pressure ON

Pressure OFF

Safety valve

Setting

Manometer

Air purge

Drain

Electricity supply

Power consumption

IP protection grade

Primary circuit flow connection

Primary circuit return connection

Primary circuit connections interaxis

Apartment heating circuit flow connection

Apartment heating circuit return connection

Tank integration flow connection

Tank integration return connection

Apartment heating circuit connections interaxis

Heating safety valve discharge connection

Filling loop connections

External dimension

Gross weight

Net weight

1)

Value whitout heat meter

2)

Specific graphics for «Primary pressure losses»

3)

Specific graphics for «Heating residual head»

4)

With 80 °C on primary circuit and ΔT 20 °C on heating circuit

5)

Other setting on demand

YES

YES

Connessione mandata circuito primario

Connessione ritorno circuito primario

Interasse connessioni circuito primario

Connessione mandata riscaldamento appartamento

Connessione ritorno riscaldamento appartamento

Connessione mandata serbatoio di accumulo

Connessione ritorno serbatoio di accumulo

Interasse connessioni riscaldamento appartamento

Connessione scarico valvola di sicurezza

Connessioni ciclo di riempimento

Dimensioni esterne

Peso lordo

Peso netto

1)

Valore senza contatore di calore

2)

Grafici specifici per le «Perdite di carico circuito primario»

3)

Grafici specifici per le «Prevalenza residua circuito riscaldamento»

4)

Con 80 °C sul circuito primario e un ΔT 20 °C sul circuito riscaldamento

5)

Altre impostazioni su richiesta

3/4” M

3/4” M

70 mm

3/4” M

3/4” M

140 mm

Tubo di rame Ø15 mm

1/2” M

550 x 450 x 240 mm

21,5 kg

21,0 kg