Linea di teleriscaldamento PREMANT

Posa senza precarica

PRE 6.241

H = 1.0 m

Lmax

Fr‘

m

kN/m

m

17

2.2

14

21

2.2

17

22

2.7

18

25

2.7

21

31

3.0

26

35

3.4

30

40

4.0

33

46

5.0

39

50

5.7

42

60

6.3

50

69

8.1

58

74

10.4

63

87

11.9

74

85

13.3

72

96

15.2

82

95

17.2

81

93

19.7

79

Lmax, spessore isolamento 1

Spessore isolamento 1

Diametro Tubo in acciaio

nominale d x s

DN

mm

20

26.9 x 2.6

25

33.7 x 2.6

32

42.4 x 2.6

40

48.3 x 2.6

50

60.3 x 2.9

65

76.1 x 2.9

80

88.9 x 3.2

100

114.3 x 3.6

125

139.7 x 3.6

150

168.3 x 4.0

200

219.1 x 4.5

250

273.0 x 5.0

300

323.9 x 5.6

350

355.6 x 5.6

400

406.4 x 6.3

450

457.2 x 6.3

500

508.0 x 6.3

Tubo guaina

D

mm

90

90

110

110

125

140

160

200

225

250

315

400

450

500

560

630

710

H = 0.6 m

Lmax

Fr‘

m

kN/m

28

1.3

35

1.3

37

1.6

42

1.6

51

1.9

58

2.1

65

2.4

75

3.1

81

3.5

97

3.9

110

5.1

118

6.6

136

7.6

133

8.5

149

9.8

147

11.2

143

12.8

H = 0.8 m

H = 1.2 m

Lmax

Fr‘

kN/m

2.6

2.6

3.2

3.2

3.7

4.1

4.7

5.9

6.7

7.5

9.6

12.4

14.1

15.7

17.8

20.3

23.1

altezza di copertura

forza di attrito

tensione ammessa

fattore di attrito del

peso specifico del suolo

coefficiente di pressione statica

Lmax

m

21

26

28

32

39

44

50

57

62

74

85

91

106

104

117

116

113

Fr‘

kN/m

1.7

1.8

2.2

2.2

2.5

2.8

3.2

4.0

4.6

5.1

6.6

8.5

9.6

10.9

12.5

14.2

16.3

Lmax

Lmax

0.20

H [m]

Fr‘ [kN/m]

s =190 N/mm2

m=0.5

g = 19 kN/m3

Kd = 0.463

PAN

terreno / PE

12.07.2021

Con riserva di modifiche tecniche.

H